Non-Shrink Grout: ASTM C1107 40-80 MPa

XINCHOR Engineering Team|

What Makes a Grout "Non-Shrink" — The Engineering Definition

Non-shrink grout is a pre-blended cementitious or polymer material that maintains its volume or exhibits controlled expansion during the plastic and hardening phases of cure. The term "non-shrink" does not mean zero volume change — it means the grout compensates for the natural drying shrinkage of cement paste through internal expansion mechanisms, resulting in net zero or positive volume change at the critical grout-to-substrate interface.

This distinction matters because shrinkage creates gaps between the grout and the equipment base or foundation. Even a 0.1 mm gap eliminates load transfer, causing point loading, vibration amplification, and progressive deterioration of both the grout and the foundation.

ASTM C1107 (Standard Specification for Packaged Dry, Hydraulic-Cement Grout — Nonshrink) defines non-shrink grout by three performance grades based on the expansion mechanism:

ASTM C1107 GradeExpansion PhaseHeight Change RequirementMechanism
Grade APre-hardening (plastic)0.0% to +4.0% at 1 dayGas-generating admixture
Grade BPost-hardening (early)0.0% to +0.3% at 1 to 3 daysExpansive cement or oxide
Grade CCombinationGrade A + B requirementsBoth mechanisms
Grade C is the most reliable for structural applications because it provides expansion in both the plastic and early hardening phases, ensuring the grout maintains contact with the substrate throughout the entire cure process. Our standard non-shrink grout (XQ-GR-NS) meets Grade C requirements.

Why Non-Shrink Properties Are Critical for Equipment Bases

When heavy equipment — turbines, compressors, generators, CNC machines — is bolted to a concrete foundation, the grout layer between the baseplate and the foundation serves three functions:

  • Full-area load transfer: The grout must fill 100% of the gap to distribute the equipment weight uniformly across the foundation. Any void creates a stress concentration that can exceed the concrete bearing capacity, causing local crushing.
  • Vibration damping: Equipment-generated vibration is transmitted through the grout to the foundation mass. Gaps interrupt this transmission path, causing the baseplate to "bounce" on the remaining contact points, amplifying vibration amplitude by 3 to 10 times.
  • Anchor bolt stability: The grout fills the annular space around anchor bolts, preventing lateral movement and ensuring the bolt transfers load concentrically. Without grout filling, anchor bolts can bend under lateral forces, leading to fatigue failure.
  • Non-shrink grout pouring for equipment base grouting

    Non-shrink grout ensures all three functions are maintained over the service life. Regular cement mortar shrinks 0.04 to 0.08% during hardening, which on a 600 mm wide baseplate creates a 0.24 to 0.48 mm gap at each edge — enough to eliminate 30 to 50% of the effective bearing area.

    Compressive Strength Grades: Matching Grout to Equipment Loads

    Not all non-shrink grouts are created equal. The compressive strength must be matched to the bearing pressure from the equipment:

    ApplicationRequired StrengthRecommended ProductNotes
    Light equipment (< 500 kg)40–50 MPaStandard non-shrink groutMost pumps, small compressors
    Medium equipment (500–5,000 kg)50–60 MPaXQ-GR-NS (Non-Shrink)CNC machines, medium compressors
    Heavy equipment (5,000–50,000 kg)60–80 MPaXQ-GR-HS (High-Strength)Turbines, large generators, presses
    Precision equipment80+ MPaEpoxy grout (XQ-GZ)Precision grinding machines, optical equipment
    Calculating required grout strength: Divide the total equipment weight (including dynamic loads — typically 1.5 to 3.0 times static weight for rotating equipment) by the effective bearing area (baseplate area minus bolt holes and voids). The grout compressive strength should be at least 3 times this bearing pressure. Example: a 10,000 kg machine on a 1.0 m x 0.5 m baseplate = 200 kPa static bearing. With dynamic factor 2.5 = 500 kPa. Required grout strength = 1,500 kPa = 1.5 MPa minimum. In practice, the 60 MPa minimum for heavy equipment provides a safety factor of 40, accommodating impact loads, fatigue, and long-term creep.

    Flow Properties: Self-Leveling vs. Pourable vs. Packing Consistency

    Non-shrink grout is available in three consistency levels, selected based on the gap geometry:

    ConsistencyFlow Spread (ASTM C1437)Gap ThicknessApplication Method
    Fluid / self-leveling> 300 mm25–150 mmPour from one side, flows by gravity
    Flowable / pourable250–300 mm20–75 mmPour with moderate head pressure
    Plastic / dry-pack< 200 mm10–50 mmRam into place with packing tool

    Our XQ-GR-NS achieves > 300 mm flow spread when mixed at 12 to 14% water content (by weight of dry grout). This self-leveling consistency ensures complete filling of the gap under the baseplate without vibration or rodding.

    Critical: Water content matters more than mixing time. Adding too much water increases flow but reduces strength and increases shrinkage. Adding too little water prevents self-leveling and creates voids. Always measure water by weight, not by volume.

    Cementitious vs Epoxy: When Each Non-Shrink Grout Type Wins

    The fundamental decision for equipment base grouting is between cementitious non-shrink grout and epoxy grout. Here is the practical decision framework:

    Choose cementitious non-shrink grout when:
    • Budget is a priority (5 to 8 times cheaper than epoxy)
    • Environment is clean (no chemical exposure)
    • Temperature range is moderate (above 5 degrees Celsius during placement)
    • Fire resistance is required (non-combustible rating A1/A2)
    • Gap thickness exceeds 50 mm (epoxy generates excessive heat in thick pours)
    Choose epoxy grout when:
    • Chemical exposure exists (acids, oils, solvents in food, pharmaceutical, or chemical plants)
    • Vibration is severe (epoxy's higher tensile and bond strength resist vibration cracking)
    • Zero shrinkage is critical (cementitious is "non-shrink" but not truly "zero-shrink")
    • Dynamic loads are dominant (epoxy's fatigue resistance is superior)
    • Space is confined (epoxy requires no moist curing)
    For the complete 20-property comparison between these two grout families, see our cementitious grout vs epoxy grout engineering guide.

    Standards and Specifications for Non-Shrink Grout

    Engineers specifying non-shrink grout should reference these standards:

    StandardScopeKey Requirements
    ASTM C1107Packaged dry non-shrink groutExpansion grades A/B/C, compressive strength
    EN 1504-6Anchoring of reinforcing steel barCompressive, bond, and creep requirements
    ACI 351.1RGrouting between equipment bases and foundationsPlacement procedures, testing, inspection
    GB/T 50448-2015Cement-based grouting material (China)Non-shrink, high-strength, fast-setting grades

    Our cementitious grout products are tested to both ASTM C1107 and GB/T 50448-2015, and our epoxy grout meets ASTM C579 (Standard Test Methods for Compressive Strength of Chemical-Resistant Mortars, Grouts, Monolithic Surfacings, and Polymer Concretes).

    Installation Best Practices

    From 20 years of technical support for grouting projects, these are the practices that separate successful installations from failures:

  • Saturate the foundation surface with water for 24 hours before grouting. A dry foundation absorbs water from the grout, causing rapid surface drying, incomplete hydration, and shrinkage at the interface. Wipe standing water from the surface just before pouring — the surface should be "saturated surface dry" (SSD).
  • Pour from one side only. Grout must flow continuously under the baseplate from the pouring side to the far side. Pouring from multiple sides traps air pockets in the center. Use a grout dam on the pour side to maintain head pressure and a vent on the far side to allow air escape.
  • Maintain minimum 25 mm grout thickness. Below 25 mm, cementitious grout cannot achieve full expansion and is prone to drying shrinkage. For gaps under 25 mm, use epoxy grout or precision leveling compounds.
  • Cure properly. Cementitious non-shrink grout requires 7 days of moist curing (wet burlap and plastic sheeting). Skipping this step allows drying shrinkage to overcome the expansion, negating the non-shrink property. Epoxy grout requires no moist curing.
  • Temperature control. Place cementitious grout when ambient temperature is between 5 and 35 degrees Celsius. Below 5 degrees, hydration slows dramatically. Above 35 degrees, the grout sets too fast, preventing complete flow under the baseplate.
  • Related Guides

    Request a grouting materials quote | Download technical data sheets

    Frequently Asked Questions

    What is the difference between non-shrink grout and regular cement mortar?

    Non-shrink grout contains expansion-generating admixtures (gas-generating agents and/or expansive cements) that compensate for the natural drying shrinkage of cement paste. Regular cement mortar shrinks 0.04 to 0.08% during hardening. Non-shrink grout maintains 0.0% to +0.3% net volume change per ASTM C1107, ensuring full contact between the grout and the substrate surface. Additionally, non-shrink grout is pre-blended with precise ratios of cement, aggregate, and admixtures for consistent quality, while site-mixed mortar quality varies with each batch.

    Can non-shrink grout be used underwater?

    Standard non-shrink grout is not suitable for underwater placement — the cement paste washes out in water. Our underwater grout (XQ-GR-UW) contains anti-washout admixtures (cellulose ether) that prevent dispersion, achieving 45 MPa compressive strength even when placed fully submerged. See our underwater concrete repair guide for submerged grouting procedures.

    How thick should non-shrink grout be under a baseplate?

    Minimum 25 mm for cementitious non-shrink grout (below this, expansion is insufficient and drying shrinkage dominates). Maximum 150 mm in a single pour (above this, heat of hydration can cause thermal cracking — pour in two lifts with 24-hour interval). For gaps of 10 to 25 mm, use epoxy grout or precision leveling compounds instead. The optimal range for most equipment bases is 40 to 80 mm.

    What is the shelf life of non-shrink grout?

    Our packaged non-shrink grout has a 12-month shelf life when stored in sealed bags in a dry, ventilated warehouse at 5 to 30 degrees Celsius. Moisture exposure is the primary degradation mechanism — even high humidity can cause pre-hydration of the cement and expansion agents, reducing both strength and expansion performance. Always use unopened bags and discard any bags that feel hard or lumpy.

    Does non-shrink grout need reinforcement?

    For standard equipment bases (gap thickness 25 to 150 mm), no reinforcement is needed — the grout is in compression, and its compressive strength (60 to 80 MPa) far exceeds the bearing load. Reinforcement is only needed for: very thick pours (> 200 mm), applications with significant tensile or shear loads, or when the grout is exposed to thermal cycling that could cause cracking. In these cases, steel fiber reinforcement (0.5 to 1.0% by volume) or welded wire mesh can be added.